Boost Your Productivity!Translate documents (Ms-Word, Ms-Excel, ...) faster and better thanks to artificial intelligence!
https://pro.wordscope.com
https://blog. wordscope .com
Automatic shut-off valve
Bleed-off flow control valve
Cabin pressure control valve
Control valve
Flow control unit
Flow control valve
Flow limiting device
Flow regulator valve
Maximum flow control valve
OXY FLOW control valve
Pressure control forward discharge valve
Pressure controller
Volume control valve

Traduction de «flow control valve » (Anglais → Français) :

TERMINOLOGIE
voir aussi les traductions en contexte ci-dessous
flow control valve [ volume control valve | flow regulator valve ]

soupape de régulation de débit [ soupape régulatrice de débit ]


flow control valve | flow limiting device

limiteur de debit


flow control valve | flow control unit

régulateur de débit






automatic shut-off valve | maximum flow control valve

limiteur de débit maximal | soupape de fermeture automatique


automatic shut-off valve [ maximum flow control valve ]

soupape de fermeture automatique [ limiteur de débit maximal ]


automatic shut-off valve | maximum flow control valve

soupape de fermeture | limiteur de débit maximal


bleed-off flow control valve

valve de régulation de débit [ à montage en dérivation ]


pressure control forward discharge valve | cabin pressure control valve | pressure controller

régulateur de pressurisation de la cabine
TRADUCTIONS EN CONTEXTE
280. Sealed flow control valves or other means shall be installed with a meter to limit the flow through the meter to its rated maximum flow.

280. Des soupapes scellées de contrôle du débit ou d’autres dispositifs scellés doivent être installés sur un compteur pour limiter le débit du compteur à son plein régime.


(c) no valves, pumps, flow-control valves or other equipment that may alter the temperature of the liquid are located between the meter chamber and the sensor.

c) qu'il n'y ait pas de soupape, de pompe, de valve de réglage du débit ou d'autre pièce d'équipement susceptible de faire varier la température du liquide qui soit installée entre la chambre de mesure du compteur et le capteur.


(6) Hose and hose connections located on the low pressure side of flow control or pressure reducing valves or devices, discharging to atmospheric pressure, shall be designed for a minimum working pressure of 60 psig.

(6) Les tuyaux flexibles et leurs raccords situés du côté basse pression des soupapes ou dispositifs régulateurs de débit ou monodétendeurs devront être étudiés de façon à pouvoir supporter une pression de régime d’au moins 60 livres par pouce carré au manomètre.


(4) An excess flow valve or other automatic device as prescribed in subsection (1) is not required for withdrawal connections of unrefrigerated tanks with a water capacity not exceeding 1,500 Imperial gallons, if the connection is protected by a controlling orifice not exceeding 5/16 inch diameter for vapour withdrawal and 1/8 inch diameter for liquid withdrawal, a manually operated shut-off valve, and a pressure-reducing regulator, all of which shall be assembled to the connection as prescrib ...[+++]

(4) Les soupapes d’excès de débit ou autres dispositifs automatiques prescrits au paragraphe (1) ne sont pas requis dans le cas des raccords d’extraction des réservoirs non réfrigérés dont la capacité en eau est de 1 500 gallons impériaux ou moins, si le raccord est protégé par un orifice de contrôle dont le diamètre n’excède pas 5/16 de pouce pour l’extraction de gaz ni 1/8 de pouce pour l’extraction de liquide, par une soupape d’arrêt à commande manuelle et par un régulateur manodétendeur, tous ces dispositifs étant montés sur le raccord comme il est prescrit à l’article 2.2(d), Division II de l’édition de 1958 de la brochure n 58 de l’Association nationale de protection contre ...[+++]


For more results, go to https://pro.wordscope.com to translate your documents with Wordscope Pro!
(3) An excess flow valve or other automatic device as prescribed in subsection (1) is not required for withdrawal connections of tanks with a water capacity of 1,500 Imperial gallons or less if the connection is protected by a controlling orifice not exceeding 5/16 inch diameter on vapour withdrawal and not exceeding 1/8 inch diameter on liquid withdrawal, a manually operated shut-off valve and pressure-reducing regulator, all of which are assembled to the connection as prescribed in 2.2(d), D ...[+++]

(3) Les soupapes d’excès de débit ou autres dispositifs automatiques prescrits au paragraphe (1) ne sont pas requis dans le cas des raccords d’extraction des réservoirs dont la capacité en eau est de 1 500 gallons impériaux ou moins, si le raccord est protégé par un orifice de contrôle dont le diamètre n’excède pas 5/16 de pouce pour l’extraction de gaz ni 1/8 de pouce pour l’extraction de liquide, par une soupape d’arrêt à commande manuelle et par un régulateur manodétendeur, tous ces dispositifs étant montés sur le raccordement comme il est prescrit à l’article 2.2(d), division II de l’édition de 1958 de la brochure n 58 de l’Association nationale de protection contre l’incendi ...[+++]


PCV1, PCV2 pressure control valve (Figure 9) Two pressure control valves are necessary for the twin venturi/twin orifice system for proportional flow splitting by controlling the backpressure of EP and the pressure in DT.

Papillons de réglage de la pression PCV1 et PCV2 (figure 9) Deux robinets servant à régler la pression sont nécessaires avec le système à tube Venturi double ou à orifice double devant assurer une séparation proportionnelle par réglage de la contre-pression en EP et de la pression en DT.


It may be necessary to adjust the suction-regulating valve (G) to control the nitrogen flow since it is possible that the barium carbonate precipitated during the test may block the sintered-glass discs.

Il peut se révéler nécessaire de régler la vanne régulatrice de l'aspiration (G) pour régulariser le courant d'azote car il est possible que le carbonate de baryum précipité pendant l'essai engorge les disques en verre fritté.


It may be necessary to adjust the suction-regulating valve (G) to control the nitrogen flow since it is possible that the barium carbonate precipitated during the test may block the sintered-glass discs.

Il peut se révéler nécessaire de régler la vanne régulatrice de l'aspiration (G) pour régulariser le courant d'azote car il est possible que le carbonate de baryum précipité pendant l'essai engorge les disques en verre fritté.


Flow control valves and flow-meters are needed in order to obtain the flow-rates required for sampling.

Des régulateurs de débit et des débitmètres sont nécessaires pour obtenir les débits requis pour le prélèvement.


The proportional sample is achieved by sampling with pump, flow-meter and flow control valve at a constant flow-rate.

On obtient l'échantillon proportionnel en opérant un prélèvement à débit constant, au moyen d'une pompe, d'un débitmètre et d'une vanne de réglage du débit.




datacenter (1): www.wordscope.fr (v4.0.br)

'flow control valve' ->

Date index: 2022-02-10
w